9801
The EPTA® 9801 relief valve (fail close FC- fail open FO) is used mainly in gas lines as blocking or venting system depending on the configuration of the actuator and the installed peripheral elements.
This line is pneumatically operated using an actuator to diaphragm and antagonistic spring.
It has an open-close indicator and its opening time is more than a 30 seconds and their closing time is less than 1 second, it can be normally open (vent) or normally close (blocking) depending on the actuator.
- Descripción
Descripción
FEATURES | |
Models | 9801 |
Variant | 9801C-NA (Compensated, Normally Open)
9801C-NC (Compensated, Normally Close) 9801D-NA (Unbalanced, Normally Open) 9801D-NC (Unbalanced, Normally Close) |
Diameter of the Valve | From Ø 1/2″ to 12″ |
Type of Connections | Thread: NPT Female standard ASME B16.11
Flange:#150 RF standard ASME B16.5 |
Type of Inner Parts | Standard |
Control Characteristics | Quick Opening |
Fail Position | Open / Close |
Type of Body | Globe |
Material of the Body | Molten Steel ASTM A216-WCC |
Watertightness | Class VI standard FCI 70-2 |