VD277

The EPTA® VD277 fail to open (FTO) pressure regulating valve is a model designed for and in distribution networks. The operating principle is based on the pressure difference on the diaphragm provided by the regulation. It has an external regulation pilot, an external variable restrictor and a filter F250. All the elements are provided installed and interconnected.

SKU: FTC-VD277_06-16 Categorías: , ,

Descripción

FEATURES
TYPE Regulating fail open (FTO); (FA); (FO)
Models VD277 (for special models ask the sales department)
Variants VD277S ; VD277S/AR; VD277A (On demand)
Diameter of Valves Ø1″ to Ø6″ (Ø8” ask the sales department)
Type of Connections Thread: NPT female up to Ø 2″, standard ASME B16.11

Flange: #150 RF, # 300 RF, # 600 RF, standard ASME B16.5

Maximum Inlet Pressure 100 Kg/cm²
Reduced Pressure Range From 0,02 Kg/cm² to 50 Kg/cm² for VD277.

From 1 Kg/cm² to 50 Kg/cm² for VD277H; for reduced pressures over

51Kg/cm² ask the manufacturer

Pressure Relief Range From 2 Kg/cm² to 15 Kg/cm², for VD277A
Control Characteristics On demand
Operation With Pilot P68S/2
Type of Body Globe
Material of the Body Molten Steel ASTM A216-WCC (special materials on demand)
Watertightness Class VI standard FCI 70-2
Optional Pre- Reducer